    Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    As some of you my know, I plan on running three 20A circuits to my system this fall, using a 60A subpanel and three 20A breakers via 10/2 Romex. From what I have read, this seems to be the best approach anyway.

    Also in my research, I have come across a couple of items from Environmental Potentials, specifically the EP-2050-EE power conditioner and EP-2750 ground filter. I was thinking these would be a good add-on for the dedicated subpanel.

    For outlets, I'm thinking I'll go with Hubbell IG8300's which have isolated grounds. Not exactly sure what the means as far as the outlets are concerned, but saw several people mention over others, not to mention they accept 10 AWG cable.

    Is there anything else I should consider? Would a whole home surge protector from the power company (TECO in my case) be good? Not really too concerned with price as I want it to be done right the first time, and labor will be paid for in a cook-out. It's good to have an electrician as a friend!
    Pass Labs XP-20 | Auralic Altair G1 | Odyssey Audio Stratos Monoblocks | JVC XL-Z411 | Nakamichi DR-1 | Technics SL-1700MK2 | Magnepan 1.7i | SVS PB-1000 Pro x 2

  2. #2
    Junior Member
    Join Date
    Sep 2023
    Location
    United States
    Posts
    17

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    The Isolated Ground outlets are grounded to remove noise, the “Yokes” (the 2 prongs) are electrically isolated from the ground screw, so the yokes and ground screw can be used for two separate ground paths.

    I am also in Florida (FPL is our company), we have the whole home surge protector. I honestly could not tell you if its worth it or not, during a hurricane in 2015 an electrical surge fried our refrigerators circuit board, so the “whole home surge protector” didn’t protect it in that instance. If you’re running a stand alone sub panel, are you pulling your line supply off the existing home sub panel or running a new line from the main (would think you would have a separate meter). I would think a good power conditioner would cover your needs (McIntosh MCP-1500 is what I’m using). The Absolute Sound has a good write up on their top power conditioners, should you feel the need.

  3. #3
    Senior Member
    Join Date
    Sep 2017
    Location
    Atlanta
    Posts
    388

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    I have a similar set up to the one you are considering in my home. I installed the Environmental Potentials on both the box feeding my music room and the one feeding the rest of the house. They come very highly recommended and while I don't have an a/b because I installed them when the box went in, I "think" they also lowered the noise floor. You are doing it the right way - due to some COVID level electrical work, I had to have some stuff redone recently and when I got it all straightened out, the noise floor was significantly lower - quite noticeably. My other unsolicited advice is to check the breaker box that gets installed and be sure it has a copper buss bar. The cheapos from Home Depot don't and that breaker box made a significant difference in the noise floor in the room (my COVID electrician didn't install what was spec'd, so I had to replace it). Of course, one can get quite elaborate audio breaker boxes (see KingRex and AudioUltra, likely among others), but the copper buss in a Siemens box made a positive difference for me without spending much more money.
    Amplification: DartZeel 468 (2) // DartZeel NHB18NS Mk. II
    Tuner: MagnumDynalab 108T/SE
    Table/Cart: J.Sikora Reference // Integrity HiFi Tru-Glider - DSAudio GrandMaster EX // Integrity HiFI Tru-Glider - Ortofon A Mono
    Equalizer/Phono Pre: DSAudio Master3
    Speakers: TAD R-1 MkII, REL Six Pack of REL Carbon Specials
    Power: Nordost QBase8 Mk3, QX4, Qkore1, 3 and 6 (chassis), QK1 (2), QV2 (2), Chord GroundAray (signal), Chord Line Aray (3), Chord Professional, AddPOWR EAU2 (2)
    DAC/Serv-stream: LampiZator Horizon/ Taiko Extreme
    Elrod Master Statement Diamond SE Speaker Cables
    Elrod Master Statement Diamond PCs (7), Evolution Acoustics 50 ohm (Zeel Connection), Nordost Odin2 IC (2), Nordost Valhalla II USB, CH Acoustic X20 IC, Final Touch Audio Elara PCs (6)
    AudioDesk Systeme RCM
    CMS Ultra 2.0 Footers TT (2) and TD (2), Revopods (2) and SortKones and EVPs where they work
    Critical Mass Systems Ultra-Q Rack > Silence Focus Amp Stands

  4. #4
    Senior Member
    Join Date
    Feb 2016
    Location
    west Michigan
    Posts
    713

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    I have both the EP 2050 + EP 2750 installed for several years now.
    When they were installed I did not notice any change in sound quality.
    They are heavy duty industrial products.
    As for your newly proposed AC circuit, #10 romex is only rated at 30 amps.
    If your sub panel has a "main" breaker of 60 amps this could be a problem. It is my understanding that wire size capacity must be appropriate to the rated breaker size.
    My System
    Acoustic Revive RTP-4
    Innuos Pulsar
    Lampizator BALTIC4
    Cary SLP-05
    Pass XA30.5 or
    Line Magnetic 845ia
    Reference 3A Reflector's
    Pr SVS SB3000 Subs
    Cables & Tubes "subject to change without notification".
    Complete system on battery power/solar
    Core Audio Design Rack
    DIY bass traps and custom curved diffusors.

  5. #5

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by jadedavid View Post
    I have both the EP 2050 + EP 2750 installed for several years now.
    When they were installed I did not notice any change in sound quality.
    They are heavy duty industrial products.
    As for your newly proposed AC circuit, #10 romex is only rated at 30 amps.
    If your sub panel has a "main" breaker of 60 amps this could be a problem. It is my understanding that wire size capacity must be appropriate to the rated breaker size.
    I think you are confusing things. The wire gauge has to be rated for the breaker it is wired to. If you are wiring a circuit to a 20A breaker, the wire gauge has to be rated for 20A. Using a wire gauge that is suitable for 30A on a 20A breaker is overkill. If you are running wiring to feed a 60A box, the wire would be a much larger gauge to in order to support supplying 60A to the main breaker.
    Micro Seiki SX-8000 air bearing table, SME 312s arm, SME 3012R arn, Dynavector XV-1s cartridge, Lyra Etna SL cartridge, ARC Ref 3 phono stage, Otari MX-55 2 track R2R, Ampex 350 tape repros, Roon Nucleus Plus music server, HiFi Rose 150B DAC, ARC Ref 6, ARC Ref 75 with KT-150s, Parasound JC5 amp , JBL 4345 speakers, Viero Equilibro Level 3 speaker cables, and Definitive Technology Ref subs.

    Reviewer for Positive Feedback

  6. #6
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Isolated Ground receptacles are sometimes used in metal conduit (ridge or flexible) systems. They would serve no purpose in a Romax® system. There are no leakage, ground, noise or lost neutral currents from other circuits in a Romax® system. By the way, use real SouthWire Romax® not generic NM-B.

    Darn few home audio systems need more than one 20 Amp circuit, but if you must:
    Run a feeder to a point near the audio equipment and use a 6 breaker box, not a sub-panel.
    Only use the Safety Ground (EGC) wire that is internal to the ROMAX®, do not add other wires.

  7. #7
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by jadedavid View Post
    ...................
    As for your newly proposed AC circuit, #10 romex is only rated at 30 amps.
    If your sub panel has a "main" breaker of 60 amps this could be a problem. It is my understanding that wire size capacity must be appropriate to the rated breaker size.
    As 'mep' noted. It's the upstream or source breaker size that matters, with reference to the cable AWG.
    Often a 100 Amp main panel can have two dozen 20 Amp breakers in it.

  8. #8
    Junior Member
    Join Date
    Sep 2023
    Location
    United States
    Posts
    17

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Watched an interesting video yesterday, its on The Absolute Sounds YouTube channel: “ Michael Fremer Updates His House Ground For Sonic Performance”. He does a good job of going through the step by step process of isolating his music room on a separate sub panel. Hope that helps you further in your quest for audio supremacy!

  9. #9
    Senior Member
    Join Date
    Feb 2016
    Location
    west Michigan
    Posts
    713

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by mep View Post
    I think you are confusing things. The wire gauge has to be rated for the breaker it is wired to. If you are wiring a circuit to a 20A breaker, the wire gauge has to be rated for 20A. Using a wire gauge that is suitable for 30A on a 20A breaker is overkill. If you are running wiring to feed a 60A box, the wire would be a much larger gauge to in order to support supplying 60A to the main breaker.
    Perhaps you have misunderstood my post.
    We are in agreement.
    I was only pointing out that running a #10 wire to a sub panel "That has a 60 amp main breaker" is not code.
    As stated, wire size must match breaker rating.
    However if the sub panel does not have a "main" breaker then running the #10 and having several branch circuits is acceptable.
    My System
    Acoustic Revive RTP-4
    Innuos Pulsar
    Lampizator BALTIC4
    Cary SLP-05
    Pass XA30.5 or
    Line Magnetic 845ia
    Reference 3A Reflector's
    Pr SVS SB3000 Subs
    Cables & Tubes "subject to change without notification".
    Complete system on battery power/solar
    Core Audio Design Rack
    DIY bass traps and custom curved diffusors.

  10. #10
    Senior Member
    Join Date
    Nov 2018
    Location
    Auburn, Washington USA
    Posts
    422

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Late last year I posted about a grounding and electrical upgrade done by Rex and Ed. Of course not everyone has the luxury or the availability of dedicated and passionate audiophile people to assist in improving their home electrical grounding and rooms power needs. But, the benefits can be heard. And the need to look for new boxes and devices from a outlet in a listening room are greatly reduced.

    Here is a link:

    Getting my electrical house, stereo room in order
    Speakers: Magico S3 (23')
    Integrated:Gryphon Diablo 300 plus DAC
    Streamer: HiFi Rose RS150b
    CD/DVD: Oppo 205
    Cables: Cardas-Shunyata-AudioQuest-Supra
    Roon Core: sonicTransporter i7 powered with HDPlex 200w linear PS, running AudioLinux for Roon--Tidal and Qobuz with iPad Pro

    Time is just a tool humans created to measure movement and record events

  11. #11
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by jadedavid View Post
    Perhaps you have misunderstood my post.
    We are in agreement.
    I was only pointing out that running a #10 wire to a sub panel "That has a 60 amp main breaker" is not code.
    As stated, wire size must match breaker rating.
    However if the sub panel does not have a "main" breaker then running the #10 and having several branch circuits is acceptable.
    Once again:
    It's the from panel breaker that matters, not the towards panel breaker.
    If the main panel has a 30 Amp breaker for the 10AWG wires, that is correct.

  12. #12
    Senior Member
    Join Date
    Feb 2016
    Location
    west Michigan
    Posts
    713

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Speedskater View Post
    Once again:
    It's the from panel breaker that matters, not the towards panel breaker.
    If the main panel has a 30 Amp breaker for the 10AWG wires, that is correct.
    Wouldn't pass code in my neck of the woods.
    Perhaps it's different where you live
    My System
    Acoustic Revive RTP-4
    Innuos Pulsar
    Lampizator BALTIC4
    Cary SLP-05
    Pass XA30.5 or
    Line Magnetic 845ia
    Reference 3A Reflector's
    Pr SVS SB3000 Subs
    Cables & Tubes "subject to change without notification".
    Complete system on battery power/solar
    Core Audio Design Rack
    DIY bass traps and custom curved diffusors.

  13. #13
    Senior Member
    Join Date
    Sep 2022
    Location
    memphis/chicago
    Posts
    171

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Speedskater View Post
    Once again:
    It's the from panel breaker that matters, not the towards panel breaker.
    If the main panel has a 30 Amp breaker for the 10AWG wires, that is correct.
    that is correct most of the time, however, it really depends on distance and overall load, typically folks run 8ga for a 30a to be on the safe side.
    Burmester 911mk3 amplifier
    Burmester 077 pre-amp
    Burmester 217 turntable system
    Burmester 111 streamer
    Burmester 948 conditioner
    Master Artist Signature Full Range Towers
    Master Artist Signature Rack
    Espirit Eureka cables
    Silent Angel NX Network Switch

  14. #14
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Porsche View Post
    that is correct most of the time, however, it really depends on distance and overall load, typically folks run 8ga for a 30a to be on the safe side.
    Yep, one step AWG oversize is always a good plan. Sometimes oversize is required for: extra long runs, or high ambient temperatures or high conduit fill.

  15. #15
    Senior Member
    Join Date
    Mar 2016
    Location
    Winter Haven, FL
    Posts
    1,503

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Sorry everyone for not responding sooner. Been a hectic week at work, which is a good thing of course.

    Anyway, when I'm talking about 10 AWG Romex, dedicated 20A runs and a 60A subpanel, of course I'm referring to the 20A runs to the listening room being run with the 10 AWG Romex FROM the subpanel. Of course, getting power TO the subpanel which will be right along side the main panel, will use heavier gauge wire.

    There have been talks that IF we can manage to get power directly from the meter before it reaches the main panel, that would be the best route, and use something on the order of 2 AWG. And yes, I know that is most likely WAY overkill, but I have a new friend that I can get the 2 AWG from cheap. In fact, it's the same "friend" that I purchased my Pass XP-20 from.

    I'm still on the fence about surge protectors and such. Maybe the Environmental Potentials units, or something from the electric company, or maybe something from SquareD, Eaton, Siemens?

    Outlets, though necessary, are low on the priority list at the moment. As long as I get solid, clean power to where it's needed, that's my main concern. With that said, I have been notified about some good quality, modified Hubbell units such as Cruze Maestro outlets and Hubbell Cryo outlets from Take Five Audio. Then again, just about every "audiophile" outlet out there is a modified Hubbell outlet, 5200/5300/8300 series.
    Pass Labs XP-20 | Auralic Altair G1 | Odyssey Audio Stratos Monoblocks | JVC XL-Z411 | Nakamichi DR-1 | Technics SL-1700MK2 | Magnepan 1.7i | SVS PB-1000 Pro x 2

  16. #16
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Thumbs up Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by chops View Post
    Sorry everyone for not responding sooner. Been a hectic week at work, which is a good thing of course.
    ..............................
    There have been talks that IF we can manage to get power directly from the meter before it reaches the main panel, that would be the best route, and use something on the order of 2 AWG.
    Don't let the inspector or your insurance know, that you're breaking the law.

    I'm still on the fence about surge protectors and such. Maybe the Environmental Potentials units, or something from the electric company, or maybe something from SquareD, Eaton, Siemens?
    Use the same brand as the panel.

    Then again, just about every "audiophile" outlet out there is a modified Hubbell outlet, 5200/5300/8300 series.
    Stock off-the-shelf Hubbell's would be a good plan.

  17. #17
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Note that 'cryo' treating the receptacles, will invalidate their 'UL' listing and could damage their plastic parts.

  18. #18
    Senior Member
    Join Date
    Mar 2016
    Location
    Winter Haven, FL
    Posts
    1,503

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Speedskater View Post
    Don't let the inspector or your insurance know, that you're breaking the law.
    How would that be breaking the law? I said after the meter, not before it.

    Besides, my friend (licensed electrician for 35+ years) wouldn't do anything illegal anyway, nor would I want him to.
    Pass Labs XP-20 | Auralic Altair G1 | Odyssey Audio Stratos Monoblocks | JVC XL-Z411 | Nakamichi DR-1 | Technics SL-1700MK2 | Magnepan 1.7i | SVS PB-1000 Pro x 2

  19. #19
    Senior Member
    Join Date
    Mar 2016
    Location
    Winter Haven, FL
    Posts
    1,503

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Speedskater View Post
    Note that 'cryo' treating the receptacles, will invalidate their 'UL' listing and could damage their plastic parts.
    Honestly, I couldn't care less about them being "cryo", and frankly think it's a bunch of hoopla anyway and does nothing for sound or "electrical flow".
    Pass Labs XP-20 | Auralic Altair G1 | Odyssey Audio Stratos Monoblocks | JVC XL-Z411 | Nakamichi DR-1 | Technics SL-1700MK2 | Magnepan 1.7i | SVS PB-1000 Pro x 2

  20. #20
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by chops View Post
    How would that be breaking the law? I said after the meter, not before it.
    Besides, my friend (licensed electrician for 35+ years) wouldn't do anything illegal anyway, nor would I want him to.
    It has to connect after the main breaker in the main panel.

  21. #21
    Senior Member
    Join Date
    Mar 2016
    Location
    Winter Haven, FL
    Posts
    1,503

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    Quote Originally Posted by Speedskater View Post
    It has to connect after the main breaker in the main panel.
    Well I probably just misunderstood him or someone else that described their setup to me. The last I spoke with him was a few months back, and I have a lot of people PM'ing me about this subject lately on several forums.

    Give me a car and I can run through the entire electrical system with my eyes closed. Put me in a house and have me deal with electrical... Well, I won't get far. LOL
    Pass Labs XP-20 | Auralic Altair G1 | Odyssey Audio Stratos Monoblocks | JVC XL-Z411 | Nakamichi DR-1 | Technics SL-1700MK2 | Magnepan 1.7i | SVS PB-1000 Pro x 2

  22. #22
    Senior Member
    Join Date
    May 2017
    Location
    Cleveland, Ohio, USA
    Posts
    531

    Re: Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

    When you see the electrician, you don't need a sub-panel, just use a 6 breaker box.

AudioShark - The Best High End Audio Discussion forum.

AudioShark forum is a leading forum site for High End Audio Discussion, Stereo System Discussion, Home Theater System Discussion, Best Home Stereo System Discussion, Home Theater Installation Discussion etc.

The AudioShark forum was created for sharing the passion of high-end Audio. We have Audiophiles from all over the world participating and sharing their knowledge. From novice to experts, you will find a friendly environment for discussing about High End Audio, Stereo System, Home Theater System, Home Stereo System, Home Theater Installation, Amplifiers, Speakers, Subwoofers, Integrated System, Acoustic treatments & Digital Room Corrections and many more.

At AudioShark, we also have incorporated an exciting Marketplace where members can peruse terrific buys on used gear, as well as meet dealers and discuss the purchase of new gear.

We are as crazy about this hobby as you are! So come on in and join us! Audioshark.org the Friendliest Audio Forum!

Industry Participation Disclosure : The owner and administrator of Audioshark is the owner of Suncoast Audio LLC in Sarasota Florida. Suncoast Audio has a full brick and mortar presence in Sarasota with several great show rooms with many world class brands. More information can be found at http://www.suncoastaudio.com

Audioshark is a community of like minded individuals. Audioshark welcomes participation from all manufacturers and owners of all brands and products. It is our belief that online forums provide a community of like minded audiophiles and music lovers to encourage the growth of this wonderful hobby.

Sincerely,
The Audioshark.org Team

Whole Home Surge Protection/Power Conditioning for Dedicated 20A lines...

Posting Permissions

  • You may not post new threads
  • You may not post replies
  • You may not post attachments
  • You may not edit your posts
  •